Sizing a solar PV system correctly is both an engineering and economic calculation. Undersize it and the system fails to meet the load. Oversize it and the client overpays for capacity they will never use. This guide walks through the standard approach used by solar engineers.
Step 1: Determine Daily Energy Consumption
- Rated power (watts)
- Daily hours of use
Daily Energy (Wh) = Σ (Watts × Hours/day)
For example: 5 LED lamps × 10W × 6h = 300Wh. Sum all appliances to get Total Daily Load.
For grid-tied systems with billing data available: use the monthly kWh figure from the electric bill and divide by 30 to get average daily consumption.
Step 2: Account for System Losses
- Inverter efficiency (~96%)
- Wiring losses (~3%)
- Soiling and shading (~5%)
- Battery round-trip losses (for off-grid, ~80%)
Design Daily Energy = Total Daily Load / System Efficiency
Step 3: Determine Peak Sun Hours (PSH)
- Metro Manila, Philippines: ~4.5–5.0 PSH
- Dubai, UAE: ~5.5–6.0 PSH
- Sydney, Australia: ~4.5–5.0 PSH
- Mumbai, India: ~5.0–5.5 PSH
- London, UK: ~2.5–3.0 PSH
Use PVGIS or NASA SSE for site-specific data.
Step 4: Calculate Required Array Size (kWp)
Array Size (kWp) = Design Daily Energy (Wh) / (PSH × 1000)
Convert to kWp by dividing by 1,000 (since 1 kWp produces 1 PSH × 1 kWh per day in ideal conditions).
Step 5: Determine Panel Count
Number of Panels = Array Size (Wp) / Panel Rated Power (Wp)
Round up to the nearest whole number. For a 4.8kWp system using 400Wp panels: 4800/400 = 12 panels.
Step 6: Size the Inverter
For grid-tied systems: inverter kW should match the array kWp ±10%. For off-grid: inverter must handle the peak load (all appliances that could run simultaneously).
Step 7: DC/AC Protection
Design the DC side (string protection): DC SPD class II at the combiner box, DC MCB per string. Design the AC side: AC SPD at the inverter output, MCCB or MCB in the AC distribution panel.
Step 8: Battery Sizing (Off-Grid)
Battery Capacity (Ah) = Daily Energy (Wh) × Days of Autonomy / (Voltage × DoD)
Where DoD = Depth of Discharge (0.5 for lead-acid, 0.8 for lithium). Days of Autonomy is typically 1–2 days for Philippines applications (short cloudy periods).
Financial Estimate
Payback period = System Cost / Annual Savings Annual Savings = Annual Generation (kWh) × Grid Rate (₱/kWh) Annual Generation = Array Size (kWp) × PSH × 365 × System Efficiency