Plumbing Pipe Sizing Using Hunter's Method

How to determine water supply pipe sizes for any building using the Water Supply Fixture Unit (WSFU) method developed by Roy B. Hunter.

Hunter's Method is the standard approach for sizing water supply piping in buildings. Developed by Roy B. Hunter of the National Bureau of Standards in 1940, it remains the basis of the Uniform Plumbing Code (UPC) and Philippine Plumbing Code pipe sizing tables.

What is a Water Supply Fixture Unit (WSFU)?

  • Lavatory: 1 WSFU
  • Water Closet (flush valve): 6 WSFU
  • Water Closet (flush tank): 2.5 WSFU
  • Bathtub: 2 WSFU
  • Shower: 2 WSFU
  • Kitchen sink: 2 WSFU
  • Washing machine: 2 WSFU
  • Urinal (flush valve): 5 WSFU

Step 1: Count Fixtures and Assign WSFUs

Create a fixture schedule. Multiply the count of each fixture type by its WSFU value and sum all items:

Total WSFU = ฮฃ (Fixture Count ร— WSFU per Fixture)

Step 2: Convert WSFU to Peak Flow Rate

Using Hunter's Curve (or the equivalent UPC Table A-1), look up the peak probable flow rate in gallons per minute (GPM) or liters per second (L/s) corresponding to your total WSFU count.

Hunter's Curve is non-linear โ€” the probability of simultaneous use decreases as fixture count increases, so doubling the fixtures does not double the flow.

Step 3: Determine Pipe Sizes

  • Velocity: 0.6โ€“3.0 m/s (2โ€“10 ft/s) for supply pipes
  • Friction loss: โ‰ค 4 m/100m of pipe (for buildings up to 10 storeys)

For each branch of the distribution system, reduce the WSFU count to only the fixtures served by that branch and repeat the flow calculation.

Step 4: Verify Available Pressure

  1. Static head (elevation ร— 9.81 kPa/m)
  2. Friction losses in the longest pipe run
  3. Minimum residual pressure at the most demanding fixture (typically 100 kPa for flush valves, 70 kPa for taps)
Available Pressure = Supply Pressure โˆ’ Static Head โˆ’ Friction Losses โ‰ฅ Minimum Required

If pressure is insufficient, upsizing pipes or adding a booster pump is required.

Drainage Pipe Sizing

  • Lavatory: 1 DFU
  • Water closet: 3โ€“4 DFU
  • Floor drain: 2 DFU
  • Kitchen sink: 2 DFU

Minimum drain pipe slopes are 2% (1:50) for horizontal runs. Stack sizes depend on total DFU load per storey and the entire stack.

Using EngEst Pro

EngEst Pro's Plumbing Calculator implements Hunter's Method automatically. Add your fixture schedule, enter supply pressure and pipe run lengths, and the platform computes WSFU totals, peak flow rates, supply pipe sizing by branch, and outputs a complete plumbing BOM including PPR supply pipes, PVC drainage pipes, fittings, and equipment โ€” all with local currency pricing.

Try it in EngEst Pro โ€” free

EngEst Pro automates everything described in this guide. Create a free account โ€” 5 projects/month, all 8 calculators, PDF BOQ export. No credit card required.

Create Free Account โ†’โ† More Guides

Related Guides

โšก
How to Calculate Electrical Load for a Residential Building
Electrical ยท 8 min read
โ†’
๐Ÿ“‹
Understanding Bill of Quantities (BOQ) in Construction
Estimating ยท 6 min read
โ†’
โ˜€๏ธ
Solar PV System Sizing: From Load Analysis to Panel Count
Solar ยท 10 min read
โ†’