Hunter's Method is the standard approach for sizing water supply piping in buildings. Developed by Roy B. Hunter of the National Bureau of Standards in 1940, it remains the basis of the Uniform Plumbing Code (UPC) and Philippine Plumbing Code pipe sizing tables.
What is a Water Supply Fixture Unit (WSFU)?
- Lavatory: 1 WSFU
- Water Closet (flush valve): 6 WSFU
- Water Closet (flush tank): 2.5 WSFU
- Bathtub: 2 WSFU
- Shower: 2 WSFU
- Kitchen sink: 2 WSFU
- Washing machine: 2 WSFU
- Urinal (flush valve): 5 WSFU
Step 1: Count Fixtures and Assign WSFUs
Create a fixture schedule. Multiply the count of each fixture type by its WSFU value and sum all items:
Total WSFU = ฮฃ (Fixture Count ร WSFU per Fixture)
Step 2: Convert WSFU to Peak Flow Rate
Using Hunter's Curve (or the equivalent UPC Table A-1), look up the peak probable flow rate in gallons per minute (GPM) or liters per second (L/s) corresponding to your total WSFU count.
Hunter's Curve is non-linear โ the probability of simultaneous use decreases as fixture count increases, so doubling the fixtures does not double the flow.
Step 3: Determine Pipe Sizes
- Velocity: 0.6โ3.0 m/s (2โ10 ft/s) for supply pipes
- Friction loss: โค 4 m/100m of pipe (for buildings up to 10 storeys)
For each branch of the distribution system, reduce the WSFU count to only the fixtures served by that branch and repeat the flow calculation.
Step 4: Verify Available Pressure
- Static head (elevation ร 9.81 kPa/m)
- Friction losses in the longest pipe run
- Minimum residual pressure at the most demanding fixture (typically 100 kPa for flush valves, 70 kPa for taps)
Available Pressure = Supply Pressure โ Static Head โ Friction Losses โฅ Minimum Required
If pressure is insufficient, upsizing pipes or adding a booster pump is required.
Drainage Pipe Sizing
- Lavatory: 1 DFU
- Water closet: 3โ4 DFU
- Floor drain: 2 DFU
- Kitchen sink: 2 DFU
Minimum drain pipe slopes are 2% (1:50) for horizontal runs. Stack sizes depend on total DFU load per storey and the entire stack.
Using EngEst Pro
EngEst Pro's Plumbing Calculator implements Hunter's Method automatically. Add your fixture schedule, enter supply pressure and pipe run lengths, and the platform computes WSFU totals, peak flow rates, supply pipe sizing by branch, and outputs a complete plumbing BOM including PPR supply pipes, PVC drainage pipes, fittings, and equipment โ all with local currency pricing.