🔥 Fire Protection · 9 min read

FDAS Fire Detection System Design per NFPA 72 and RA 9514

A practical guide to designing a Fire Detection and Alarm System (FDAS) for residential, commercial, and industrial buildings — covering detector spacing, FACP sizing, and BOM computation.

A Fire Detection and Alarm System (FDAS) is a life-safety system required in all commercial, industrial, and multi-unit residential buildings under Philippine Fire Code RA 9514 and NFPA 72 (National Fire Alarm and Signaling Code). Correct design starts with understanding the building, selecting the right system type, and computing device counts per the applicable code.

System Types

  • Conventional FDAS: Devices are grouped into zones. A fault or alarm in a zone triggers that zone's indicator on the Fire Alarm Control Panel (FACP). Suitable for smaller buildings (up to ~20 zones).
  • Addressable FDAS: Each device has a unique address. The FACP can identify exactly which device is in alarm or fault. Required for buildings over 10 storeys or where RA 9514 mandates it.

Step 1: Classify the Building

  • Light Hazard: Residences, offices, schools — smoke detectors at 9.3 m² (100 ft²) spacing
  • Ordinary Hazard: Retail, restaurants, warehouses — smoke detectors at 6.5 m² (70 ft²) spacing
  • High Hazard: Industrial, flammable storage — heat detectors required in addition to smoke

Step 2: Detector Placement

  • Maximum spacing: 9.3 m (30 ft) center-to-center for low-ceiling, open areas
  • Adjust for high ceilings, beams, and air supply interference
  • Place within 150 mm (6 in) of the apex in peaked ceilings
Number of Detectors = Room Area / Maximum Spacing Area

Round up. For irregular rooms, divide into rectangular zones and compute each separately.

Heat detectors are used in locations where smoke detectors are not suitable — kitchens, boiler rooms, parking garages. Maximum spacing is 6.1 m (20 ft) for standard rate-of-rise detectors.

Step 3: Manual Call Points (MCP)

RA 9514 requires MCPs (pull stations) at every exit and stairwell. Maximum travel distance to an MCP is 30 m (100 ft). Minimum one MCP per floor.

Step 4: Notification Devices

  • Horn/Strobe units: Required in all corridors, common areas, and at exits. Placed per NFPA 72 audibility requirements (75 dBA at 3 m in sleeping rooms, 65 dBA in corridors).
  • Visual strobes: Required in areas where occupants may not hear audible alarms (high-noise environments, hearing-impaired accessible areas).

Step 5: FACP Sizing

  • Conventional: 2 to 32 zones typically; select based on zone count
  • Addressable: Each loop supports up to 99–250 devices depending on manufacturer; size loops so no loop exceeds 80% capacity

Battery backup: NFPA 72 requires 24-hour standby plus 5-minute alarm. Size battery (Ah) = (Standby current × 24h) + (Alarm current × 0.083h).

Step 6: Wiring

  • Initiating Device Circuit (IDC): 1.5 mm² minimum
  • Signal Line Circuit (SLC) for addressable: per manufacturer spec (typically 1.0–1.5 mm²)
  • Notification Appliance Circuit (NAC): 1.5 mm² minimum

All wiring shall be in EMT conduit (exposed) or concealed in walls.

Using EngEst Pro

EngEst Pro's FDAS Calculator automates the entire process. Select your building type and system type, add rooms with their dimensions and occupancy — the platform auto-computes smoke detector counts, heat detector counts, MCPs, notification devices, wiring lengths, FACP sizing, and outputs a complete BOM ready for BFP permit submission.

Try it in EngEst Pro — free

EngEst Pro automates everything described in this guide. Create a free account — 5 projects/month, all 8 calculators, PDF BOQ export. No credit card required.

Create Free Account →← More Guides

Related Guides

⚡
How to Calculate Electrical Load for a Residential Building
Electrical · 8 min read
→
📋
Understanding Bill of Quantities (BOQ) in Construction
Estimating · 6 min read
→
☀️
Solar PV System Sizing: From Load Analysis to Panel Count
Solar · 10 min read
→