Manual Call Point Placement per RA 9514 and NFPA 72
Manual call points are the simplest FDAS device to lay out โ a short list of rules covers almost every building.
Where they go
- At every exit from each floor, and at each exit stair door.
- Within 1.5 m of the exit doorway, on the exit-access side.
- Additional units so travel distance to reach any call point does not exceed 60 m (200 ft) on any floor.
- At least one per floor, even a small one.
Mounting
- Operable part 1.1โ1.4 m (42โ48 in) above the finished floor.
- Clear, unobstructed, and visible; contrasting colour (red) against the wall.
- Protective cover / stopper where malicious activation is a concern (with local alarm).
Extra locations
Near special hazards โ kitchens, generator and fuel rooms, chemical stores, loading docks โ and at fire command centres and constantly-attended locations. In assembly occupancies, at stage exits and near the platform.
Addressing and circuits
On an addressable system, each call point is a point on the loop โ no separate zoning needed. On a conventional system, group call points into their own initiating zone (often combined with that area’s detectors) so the panel annunciates a manual activation clearly.
Count
EngEst Pro’s FDAS Calculator places a manual call point at every exit and adds units to meet the 60 m travel rule for each floor you define, then lists MCPs and their wiring in the FDAS BOM.