Heat Detector Spacing and Listed Spacing Adjustment

Heat detectors go where smoke detectors cannot survive or would false-alarm โ€” kitchens, boiler rooms, parking. Their spacing is tighter and drops sharply with ceiling height.

Listed spacing

Heat detectors are listed for spacings such as 15 × 15 ft (4.6 m), 25 × 25 ft (7.6 m), or 50 × 50 ft (15 m) depending on the model. The listed value assumes a ceiling height of 3.0 m (10 ft) or less.

Advertisement

Ceiling-height reduction

Because a heat plume spreads and cools as it rises, NFPA 72 requires the spacing to be reduced for higher ceilings:

Ceiling height% of listed spacing
0โ€“3.0 m100%
3.0โ€“3.7 m91%
3.7โ€“4.6 m84%
4.6โ€“5.5 m77%
5.5โ€“6.7 m71%
> 6.7โ€“9.1 m~63% and downward
Design spacing = listed spacing × height factor; then apply the 0.7 corner rule

Rate-of-rise vs fixed temperature

Where heat detection is required or preferred

Kitchens and cooking areas, mechanical and boiler rooms, laundries, parking garages, attics and concealed spaces, and any environment too dirty, humid, or fume-laden for reliable smoke detection.