🔥 FDAS / Fire · 6 min read
FACP Standby Battery Calculation — 24 Hours Plus 5 Minutes
The battery calculation is a required submittal for every FDAS. It is simple arithmetic, but every device on the system has to be in the table.
Build the current table
List every current draw in two columns — standby (quiescent) and alarm:
- Control panel and each expansion/loop card
- Every initiating device (addressable detectors, modules)
- Every notification appliance (alarm column only, at rated candela/dBA setting)
- Auxiliary relays, communicators, door holders released on alarm
Advertisement
The formula
AH = [ (Istandby × Tstandby) + (Ialarm × Talarm) ] × 1.2
- Tstandby = 24 h for a protected-premises system (60 or 72 h for some remote/central-station and voice systems — check the AHJ).
- Talarm = 5 min (0.0833 h); 15 min for voice evacuation.
- 1.2 = 20% ageing/derating margin.
Worked example
Istandby = 0.45 A, Ialarm = 3.8 A:
AH = [ (0.45 × 24) + (3.8 × 0.0833) ] × 1.2
= [ 10.8 + 0.317 ] × 1.2 = 13.3 AH → select 18 AH batteries
= [ 10.8 + 0.317 ] × 1.2 = 13.3 AH → select 18 AH batteries
Also check
- Battery charger capacity: must recharge the battery to full within 48 h while carrying standby load.
- Battery cabinet space and the panel’s maximum battery size.
- Notification booster power supplies each get their own battery calculation.
🔥 Using EngEst Pro
EngEst Pro’s FDAS Calculator totals standby and alarm current from the device schedule, applies the 24 h + 5 min + 1.2 formula, and sizes the FACP battery — the result and the devices flow into the BOM and the BFP submittal.
Put this on autopilot with EngEst Pro
Create a free EngEst Pro account — 5 projects a month, all 8 calculators, PDF BOQ export. No credit card required.
Create Free Account → Run your first estimate in under 10 minutes.