Notification design has two independent jobs โ€” be heard everywhere and be seen everywhere โ€” each with its own set of rules.

Audible coverage

SPL at distance d = SPL at reference − 20 × log₁₀(d / dref) − wall/door losses (10โ€“20 dB per closed door)
Advertisement

Visible (strobe) coverage

Strobe candela (cd) is selected from tables by room size for a wall-mounted device on one wall:

Square roomMin candela (1 strobe, centred wall)
6.1 × 6.1 m15 cd
9.1 × 9.1 m30 cd
12.2 × 12.2 m60 cd
15.2 × 15.2 m95 cd

Large rooms use multiple strobes; corridors use spacing tables (e.g. 15 cd every 30 m, first within 4.6 m of the end).

Synchronization

Where more than two strobes are visible from any point, they must flash in synchronization (photosensitive-epilepsy safety). This needs sync modules or sync-capable circuits โ€” a BOM and circuit-design item.

Load on the NAC

Total the current draw of all appliances on each Notification Appliance Circuit, add voltage-drop margin to the end of line, and confirm the panel/booster NAC rating covers it.