Sizing a Domestic Water Booster Pump — Flow and Total Dynamic Head

A booster pump is specified by two numbers — flow rate and total dynamic head. Get both and the pump curve does the rest.

Design flow

Use the peak probable flow from the fixture-unit calculation for the zone the pump serves. For a packaged multi-pump set, divide the duty across 2–3 pumps plus one standby so the set modulates with demand.

Advertisement

Total dynamic head (TDH)

TDH = Hstatic + Hfriction + Hresidual − Hsuction

Worked example

10-storey residential zone, pump in the basement, top fixture 34 m up, longest run 60 m, peak flow 3.2 L/s, fed from a ground cistern at atmospheric pressure.

Hstatic = 34 m
Hfriction = 60 m × 3 m/100 m + fittings 6 m = 7.8 m
Hresidual = 14 m (flush valves present)
TDH = 34 + 7.8 + 14 − 0 = 55.8 m ≈ 56 m

Select a booster set delivering 3.2 L/s at 56 m head, with the operating point in the middle third of the pump curve for efficiency.

Also specify

Pressure vessel volume, VFD or staged control, low-water cut-off, non-return valves, and the motor kW from the pump’s curve at the duty point.