Sizing the Grounding Electrode Conductor and Ground Rods

The grounding electrode conductor connects the service to earth. Its size comes from a short table, with one important cap for rod-only electrodes.

GEC sizing table

Largest ungrounded service conductor (copper)GEC (copper)
≤ 30 mm²8 mm²
38–50 mm²14 mm²
60–100 mm²22 mm²
125–175 mm²30 mm²
200–300 mm²38 mm²
Advertisement

The ground-rod cap

The GEC run to a made electrode (ground rod, pipe electrode) is never required to be larger than 14 mm² copper, no matter how large the service. The connection to a concrete-encased electrode is capped at 22 mm². Only the run to a metal water pipe or structural steel follows the full table.

Ground rod specification

The 25-ohm rule

A single rod electrode must be tested. If it does not achieve 25 Ω or less, a second rod is required, spaced at least 1.8 m from the first (one rod length is the practical minimum; further apart is better). Once two rods are installed, no further resistance testing is mandated by the basic rule.

What goes in the BOM

Ground rods, driving couplings and points for deep drives, exothermic weld kits or listed clamps, the GEC conductor length, and any ground bar or inspection well.