🔧 EE Tools · 6 min read

Reading PEC Table 3.10.2.6(B) — 60 °C Conductor Ampacities

THHN is a 90 °C conductor, but on most branch circuits you size it from the 60 °C column. The reason is the terminals, not the wire.

The termination temperature rule

Breakers, lugs, and equipment terminals have a temperature rating. Unless marked otherwise:

Equipment listed and marked for 75 °C terminations lets you use the 75 °C column for smaller circuits too — check the label.

Advertisement

Typical 60 °C ampacities (copper, 30 °C ambient)

Size (mm²)AWG60 °C ampacity
2.01415
3.51220
5.51030
8.0840
14655

Correction still uses the insulation column

Here is the subtlety: you select the final size from the 60 °C column, but you apply temperature and bundling correction factors to the ampacity of the conductor’s actual insulation rating (90 °C for THHN). Then you compare the corrected value back against the load, and separately confirm the 60 °C value still covers the load.

Worked example

24 A continuous load (30 A after 125%), 40 °C ambient. 90 °C correction factor ≈ 0.91.

5.5 mm²: 90 °C ampacity 40 × 0.91 = 36.4 A ≥ 30 A  ✓
5.5 mm²: 60 °C ampacity 30 A ≥ 30 A  ✓ (just)
→ 5.5 mm² is acceptable; 8.0 mm² gives comfortable margin
🔧 Using EngEst Pro

EngEst Pro’s EE Tools apply the 60 °C termination rule for circuits at or below 100 A and the 75 °C column above it, while correcting from the conductor’s true insulation rating — so the size it returns is code-consistent.

Put this on autopilot with EngEst Pro

Create a free EngEst Pro account — 5 projects a month, all 8 calculators, PDF BOQ export. No credit card required.

Create Free Account → Run your first estimate in under 10 minutes.