Ampacity Correction Factors for Ambient Temperature and Bundling

The ampacity table assumes a 30 °C ambient and no more than three current-carrying conductors. Real installations are often hotter and more crowded, and both effects reduce the usable current.

Temperature correction

Above 30 °C ambient, multiply the table ampacity by the correction factor for the conductor’s insulation rating:

Ambient60 °C conductor75 °C conductor90 °C conductor
31โ€“35 °C0.910.940.96
36โ€“40 °C0.820.880.91
41โ€“45 °C0.710.820.87
46โ€“50 °C0.580.750.82

Rooftop conduit in direct sun gets an additional ambient adder โ€” often 20โ€“30 °C on top of the design air temperature.

Advertisement

Conductor bundling adjustment

Current-carrying conductorsAdjustment factor
4โ€“60.80
7โ€“90.70
10โ€“200.50

The neutral of a balanced three-phase circuit is not counted; a neutral carrying harmonic current is.

The two factors multiply

Corrected ampacity = Table ampacity (insulation column) × Ftemp × Fbundle

Example: 22 mm² THHN, table 90 °C ampacity 95 A, in a 42 °C attic with 6 current-carrying conductors:

95 × 0.87 × 0.80 = 66 A usable

The conductor that looked like 95 A on the table is really a 66 A conductor in that location.