๐Ÿ”ง EE Tools ยท 6 min read

Wire Sizing by Ampacity vs Voltage Drop โ€” Which Governs?

Every conductor size must satisfy two independent checks โ€” carrying the current without overheating, and delivering it without excessive voltage loss. Which one forces the bigger wire depends almost entirely on run length.

Two independent checks

Advertisement

The crossover length

Set the voltage-drop equation equal to the limit and solve for length:

Lmax = (%VDlimit × Vnominal) / (k × I × Rper metre)

where k = 2 for single-phase and √3 for three-phase. Below Lmax, the ampacity-selected size is adequate; above it, you must upsize for voltage drop.

Worked comparison

40 A load, 230 V single-phase, 8.0 mm² copper (ampacity 50 A at 75 °C, R ≈ 0.00215 Ω/m), 3% limit:

Lmax = (0.03 × 230) / (2 × 40 × 0.00215) = 6.9 / 0.172 = 40 m

At 25 m the 8.0 mm² conductor is governed by ampacity and passes. At 60 m it fails voltage drop and you move to 14 mm².

Planning rule of thumb

For 230 V single-phase copper loaded near its ampacity, expect voltage drop to govern beyond roughly 25โ€“35 m. For 400 V three-phase, the higher voltage roughly doubles the allowable length. Long feeders and site-perimeter circuits are nearly always voltage-drop governed.

๐Ÿ”ง Using EngEst Pro

EngEst Pro’s EE Tools wire-sizing utility checks both criteria at once โ€” it selects the ampacity-based size, then tests voltage drop at your run length and upsizes automatically if needed, showing which criterion governed.

Put this on autopilot with EngEst Pro

Create a free EngEst Pro account โ€” 5 projects a month, all 8 calculators, PDF BOQ export. No credit card required.

Create Free Account โ†’ Run your first estimate in under 10 minutes.