Wire Sizing by Ampacity vs Voltage Drop โ Which Governs?
Every conductor size must satisfy two independent checks โ carrying the current without overheating, and delivering it without excessive voltage loss. Which one forces the bigger wire depends almost entirely on run length.
Two independent checks
- Ampacity depends on the conductor, its insulation temperature rating, ambient temperature, and how many conductors share the raceway. It does not depend on length.
- Voltage drop is directly proportional to length and current. A conductor that is fine at 10 m may violate the 3% limit at 40 m carrying the same current.
The crossover length
Set the voltage-drop equation equal to the limit and solve for length:
where k = 2 for single-phase and √3 for three-phase. Below Lmax, the ampacity-selected size is adequate; above it, you must upsize for voltage drop.
Worked comparison
40 A load, 230 V single-phase, 8.0 mm² copper (ampacity 50 A at 75 °C, R ≈ 0.00215 Ω/m), 3% limit:
At 25 m the 8.0 mm² conductor is governed by ampacity and passes. At 60 m it fails voltage drop and you move to 14 mm².
Planning rule of thumb
For 230 V single-phase copper loaded near its ampacity, expect voltage drop to govern beyond roughly 25โ35 m. For 400 V three-phase, the higher voltage roughly doubles the allowable length. Long feeders and site-perimeter circuits are nearly always voltage-drop governed.
EngEst Pro’s EE Tools wire-sizing utility checks both criteria at once โ it selects the ampacity-based size, then tests voltage drop at your run length and upsizes automatically if needed, showing which criterion governed.
Put this on autopilot with EngEst Pro
Create a free EngEst Pro account โ 5 projects a month, all 8 calculators, PDF BOQ export. No credit card required.
Create Free Account โ Run your first estimate in under 10 minutes.