PV String Sizing โ€” Panels in Series Within MPPT Voltage Limits

String sizing is a temperature problem. The panel datasheet values are at 25 °C; your roof is not, and the difference decides how many modules you can wire in series.

The two limits

Advertisement

Temperature correction

Voc(T) = Voc,STC × [1 + βVoc × (Tmin − 25)]
Vmp(T) = Vmp,STC × [1 + βVmp × (Tmax − 25)]

β is the temperature coefficient (negative, ~−0.27%/°C for Voc on modern modules). Use record-low ambient for Tmin and cell temperature up to ~70 °C for Tmax in the tropics.

Worked example

Panel: Voc 41.5 V, Vmp 34.8 V, βVoc −0.27%/°C. Inverter: max DC 600 V, MPPT 90โ€“550 V. Site: Tmin 12 °C, cell Tmax 68 °C.

Voc(12°C) = 41.5 × [1 + (−0.0027)(12 − 25)] = 43.0 V
Max panels = 600 / 43.0 = 13.9 → 13 panels

Vmp(68°C) ≈ 34.8 × [1 + (−0.0037)(68 − 25)] = 29.3 V
Min panels = 90 / 29.3 = 3.1 → 4 panels

Any string of 4โ€“13 panels works; choose the length that fits the roof and balances the MPPT inputs.