⚡ Electrical · 8 min read

Motor Feeder and Branch Circuit Sizing per PEC

Motor circuits use several different multipliers on several different base currents. Mixing them up is the classic motor-circuit error.

Start from table full-load current

The PEC requires conductor and protection sizing to use the full-load current from the code tables (by horsepower and voltage), not the motor nameplate current. The nameplate is used only for overload relay sizing.

Advertisement

Branch-circuit conductors

Iconductor = 1.25 × table FLC (single motor, continuous duty)

Select the conductor from the ampacity table at this current, then apply correction factors as normal.

Branch-circuit short-circuit and ground-fault protection

This device protects against faults, not overload, so it is sized well above FLC to ride through starting inrush:

Protective deviceMax % of table FLC
Inverse-time circuit breaker250%
Non-time-delay fuse300%
Time-delay (dual-element) fuse175%

If the motor will not start at the calculated value, it may be increased to the next standard size (up to higher code ceilings).

Overload protection

Overload setting = 1.15 to 1.25 × motor nameplate FLA

Use 125% for service factor ≥ 1.15 or a 40 °C-rise motor; 115% otherwise.

Feeder for several motors

Ifeeder = 1.25 × (largest motor FLC) + Σ(other motor FLCs)

Feeder protection = largest branch-circuit protective device rating + sum of the other motors’ full-load currents.