Lighting Design by the Lumen Method โ€” Fixtures and Circuits

The lumen method gives a defensible fixture count in a few lines of arithmetic โ€” and that count drives the lighting load, the circuits, and the BOM.

Pick the target illuminance

SpaceTarget (lux)
Corridor / storage100โ€“150
General office300โ€“500
Drawing / detailed work500โ€“750
Retail sales floor500โ€“1000
Advertisement

The lumen method formula

N = (E × A) / (F × UF × MF)

Where N = number of luminaires, E = target lux, A = floor area (m²), F = rated lumens per luminaire, UF = utilisation factor, MF = maintenance factor.

Utilisation and maintenance factors

UF comes from the manufacturer’s photometric table, indexed by the room index and surface reflectances:

Room index K = (L × W) / (Hm × (L + W))

where Hm is the mounting height above the working plane. UF is typically 0.4โ€“0.7. MF (light loss over the cleaning cycle) is typically 0.7โ€“0.8 for a normal environment.

Worked example

Office 12 m × 8 m, target 400 lux, LED panels at 4000 lm each, UF = 0.55, MF = 0.8:

N = (400 × 96) / (4000 × 0.55 × 0.8) = 38 400 / 1760 = 21.8 → 24 luminaires (6 × 4 grid)

From fixtures to circuits

At ~40 W per panel, 24 fixtures = 960 W. A 20 A, 230 V lighting circuit loaded to 80% carries ~3680 W, so this room fits one circuit with room to spare. Keep lighting circuits under 12โ€“16 outlets and separate from receptacle circuits.