⚡ Electrical · 7 min read

Power Factor Correction — Sizing a Capacitor Bank

Utilities penalise low power factor. A capacitor bank pays for itself quickly — but only if it is sized and stepped correctly.

The correction formula

To move from an existing power factor cos φ₁ to a target cos φ₂ at constant real power P:

QC (kVAR) = P (kW) × (tan φ₁ − tan φ₂)
Advertisement

Worked example

Plant load 300 kW at 0.75 PF (φ₁ = 41.4°, tan = 0.882), target 0.95 PF (φ₂ = 18.2°, tan = 0.329):

QC = 300 × (0.882 − 0.329) = 166 kVAR

Select a standard bank: 3 × 50 kVAR + 1 × 25 kVAR = 175 kVAR, or an automatic bank of 25 kVAR steps.

Fixed vs automatic

Two things that go wrong

What goes in the BOQ

Capacitor modules, contactors or thyristor switches, detuned reactors if required, the PF controller, an enclosure with ventilation, and protective fuses or breakers per step.

⚡ Using EngEst Pro

EngEst Pro computes the kVAR needed to reach your target power factor from the project’s connected load, suggests a standard step configuration, and lists the capacitor bank, reactors, and switching gear in the electrical BOM.

Put this on autopilot with EngEst Pro

Create a free EngEst Pro account — 5 projects a month, all 8 calculators, PDF BOQ export. No credit card required.

Create Free Account → Run your first estimate in under 10 minutes.