⚡ Electrical · 8 min read

Sizing THHN Conductors per PEC Table 3.10.1 — A Worked Example

Conductor sizing is where most electrical estimates go wrong — either the wire is undersized and fails inspection, or it is oversized and the bid loses. This guide works a single 230 V branch circuit end to end.

The design current

Start from the connected load and convert it to amperes. Our example is an 8 kW continuous single-phase load (a run of package air-conditioners on a dedicated sub-feed) supplied at 230 V.

I = P / V = 8000 W / 230 V = 34.8 A

The PEC requires the conductor and overcurrent device for a continuous load (running 3 hours or more) to be rated at not less than 125% of the continuous current.

Idesign = 34.8 A × 1.25 = 43.5 A

So we need a conductor with an allowable ampacity of at least 43.5 A and an overcurrent device (OCPD) of the next standard size at or above it — a 50 A breaker.

Advertisement

Reading the ampacity table

PEC 2017 Table 3.10.1.16 gives allowable ampacities for not more than three current-carrying conductors in a raceway at 30 °C ambient. THHN is a 90 °C insulation, so you may use the 90 °C column for correction math only — the final selection can never exceed the 60 °C or 75 °C termination rating.

Size (mm²)AWG60 °C75 °C90 °C
3.512252530
5.510303540
8.08405055
146556575
224708595
30385100110

Representative of common PEC practice at 30 °C ambient; confirm against the code edition enforced locally.

Applying correction factors

Required 90 °C ampacity = 43.5 A / 0.91 = 47.8 A

8.0 mm² THHN has a 90 °C ampacity of 55 A (clears 47.8 A) and a 75 °C termination ampacity of 50 A (clears the 43.5 A design current). Selection: 8.0 mm² THHN copper.

The voltage-drop check

The PEC recommends a maximum 3% drop on a branch circuit, 5% total. For a one-way run of 45 m using copper resistivity of about 0.0172 Ω·mm²/m:

Rloop = 2 × 0.0172 × 45 / 8.0 = 0.194 Ω
Vdrop = 34.8 × 0.194 = 6.7 V → 6.7 / 230 = 2.9%

Inside the limit but with no margin. On a run this long it is worth upsizing to 14 mm², which drops the loss to about 1.7% and leaves headroom for load growth.

Finishing the circuit

⚡ Using EngEst Pro

The Electrical Calculator and EE Tools run this whole sequence — enter the load schedule (type, quantity, watts, demand factor, cable run) and EngEst Pro returns the design current, corrected conductor size, breaker rating, voltage-drop percentage, and conduit size, then rolls it into an electrical BOM priced in your local currency.

Size every circuit in minutes, not spreadsheets

Create a free EngEst Pro account — 5 projects a month, all 8 calculators, PDF BOQ export. No credit card required.

Create Free Account → Run your first estimate in under 10 minutes.