Sizing THHN Conductors per PEC Table 3.10.1 — A Worked Example
Conductor sizing is where most electrical estimates go wrong — either the wire is undersized and fails inspection, or it is oversized and the bid loses. This guide works a single 230 V branch circuit end to end.
The design current
Start from the connected load and convert it to amperes. Our example is an 8 kW continuous single-phase load (a run of package air-conditioners on a dedicated sub-feed) supplied at 230 V.
The PEC requires the conductor and overcurrent device for a continuous load (running 3 hours or more) to be rated at not less than 125% of the continuous current.
So we need a conductor with an allowable ampacity of at least 43.5 A and an overcurrent device (OCPD) of the next standard size at or above it — a 50 A breaker.
Reading the ampacity table
PEC 2017 Table 3.10.1.16 gives allowable ampacities for not more than three current-carrying conductors in a raceway at 30 °C ambient. THHN is a 90 °C insulation, so you may use the 90 °C column for correction math only — the final selection can never exceed the 60 °C or 75 °C termination rating.
| Size (mm²) | AWG | 60 °C | 75 °C | 90 °C |
|---|---|---|---|---|
| 3.5 | 12 | 25 | 25 | 30 |
| 5.5 | 10 | 30 | 35 | 40 |
| 8.0 | 8 | 40 | 50 | 55 |
| 14 | 6 | 55 | 65 | 75 |
| 22 | 4 | 70 | 85 | 95 |
| 30 | 3 | 85 | 100 | 110 |
Representative of common PEC practice at 30 °C ambient; confirm against the code edition enforced locally.
Applying correction factors
- Ambient temperature. If the raceway runs through a 40 °C ceiling void, the 90 °C-column correction factor is about 0.91.
- Bundling. More than three current-carrying conductors in one raceway triggers an adjustment (0.80 for 4–6, 0.70 for 7–9). Our circuit has two, so none applies.
8.0 mm² THHN has a 90 °C ampacity of 55 A (clears 47.8 A) and a 75 °C termination ampacity of 50 A (clears the 43.5 A design current). Selection: 8.0 mm² THHN copper.
The voltage-drop check
The PEC recommends a maximum 3% drop on a branch circuit, 5% total. For a one-way run of 45 m using copper resistivity of about 0.0172 Ω·mm²/m:
Vdrop = 34.8 × 0.194 = 6.7 V → 6.7 / 230 = 2.9%
Inside the limit but with no margin. On a run this long it is worth upsizing to 14 mm², which drops the loss to about 1.7% and leaves headroom for load growth.
Finishing the circuit
- OCPD: 50 A.
- Equipment grounding conductor: ~5.5 mm² copper for a 50 A device (PEC Table 2.50.1.22).
- Raceway: 3 × 8.0 mm² (or 14 mm²) THHN plus a 5.5 mm² ground fits 20 mm (¾") conduit below 40% fill.
The Electrical Calculator and EE Tools run this whole sequence — enter the load schedule (type, quantity, watts, demand factor, cable run) and EngEst Pro returns the design current, corrected conductor size, breaker rating, voltage-drop percentage, and conduit size, then rolls it into an electrical BOM priced in your local currency.
Size every circuit in minutes, not spreadsheets
Create a free EngEst Pro account — 5 projects a month, all 8 calculators, PDF BOQ export. No credit card required.
Create Free Account → Run your first estimate in under 10 minutes.